Climate Change Data Portal
DOI | 10.1016/j.ijrefrig.2018.12.019 |
Options of low Global Warming Potential refrigerant group for a three-stage cascade refrigeration system | |
Sun, Zhili; Wang, Qifan; Dai, Baomin; Wang, Meng; Xie, Zhiyuan | |
发表日期 | 2019 |
ISSN | 0140-7007 |
EISSN | 1879-2081 |
卷号 | 100页码:471-483 |
英文摘要 | To explore the technical alternatives of refrigerant substitution and analyze the application of low GWP refrigerant in three-stage cascade refrigeration system (TCRS), the change of operation parameters with the evaporation temperature has been studied by thermodynamic analysis. The results show that R1150 can replace R14 in low-temperature cycle. R41 and R170 can replace R23 in medium-temperature cycle and R170 will be recommended as a priority. In high-temperature cycle, the refrigerants of R717, R152a and R161 are recommended. Taking into account environmental protection, the natural refrigerant of R717 is a good choice in the large refrigeration system. In particular, the refrigerant groups of R1150/R41/R717, R1150/R41/R152a, R1150/R41/R161, R1150/R170/R717, R1150/R170/R152a and R1150/R170/R161 are recognized. The results provide a basic theoretical analysis of the selection and replacement of refrigerant in TCRS. (C) 2018 Elsevier Ltd and IIR. All rights reserved. |
WOS研究方向 | Thermodynamics ; Engineering |
来源期刊 | INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
![]() |
文献类型 | 期刊论文 |
条目标识符 | http://gcip.llas.ac.cn/handle/2XKMVOVA/96200 |
作者单位 | Tianjin Univ Commerce, Tianjin Key Lab Refrigerat Technol, Tianjin, Peoples R China |
推荐引用方式 GB/T 7714 | Sun, Zhili,Wang, Qifan,Dai, Baomin,et al. Options of low Global Warming Potential refrigerant group for a three-stage cascade refrigeration system[J],2019,100:471-483. |
APA | Sun, Zhili,Wang, Qifan,Dai, Baomin,Wang, Meng,&Xie, Zhiyuan.(2019).Options of low Global Warming Potential refrigerant group for a three-stage cascade refrigeration system.INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID,100,471-483. |
MLA | Sun, Zhili,et al."Options of low Global Warming Potential refrigerant group for a three-stage cascade refrigeration system".INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID 100(2019):471-483. |
条目包含的文件 | 条目无相关文件。 |